Complete bill of materials for acoustic HVAC integration across the MediaVerse Studio Complex. All silencers, duct treatments, diffusers, and plenum materials required to achieve NC targets.
CUSTOMIZABLE — Equipment brand and model may be substituted if the replacement unit meets or exceeds the specified cooling capacity (kW), noise rating (dBA at 1m), and refrigerant type. Contractors may use preferred suppliers for duct hangers, vibration isolator brackets, and condensate fittings provided they meet the load and isolation ratings listed. Labelling, signage, and equipment tag formats may follow your company branding.
DO NOT ALTER — Total cooling capacity (7.04 kW / 205 W/m²), duct dimensions (300mm x 200mm main), silencer attenuation targets (Run A: 40 dB, B/C: 25 dB, D: 15 dB), terminal velocity limits per run, flexible connector requirements at every wall penetration, and the VRF split configuration (2 x 1.0 TR IDU). These values are acoustically engineered and changing any of them invalidates the NC budget calculations.
Four inline rectangular silencers sized to meet room-specific NC targets. All silencers are splitter-type with mineral wool fill and perforated steel facing.
| Run | Serves | Length (mm) | Cross Section | Attenuation | NC Max | Est. Cost |
|---|
| Item | Specification | Quantity | Unit | Est. Unit Cost | Est. Total |
|---|
| # | Model | Position | Airflow (m3/h) | Face Velocity (m/s) | NC Rating | Est. Cost |
|---|
| Item | Specification | Quantity | Unit | Est. Unit Cost | Est. Total |
|---|
Duct runs A through D from indoor units through silencers to each room. Main duct runs along the buffer spine ceiling plenum.
Post-installation NC verification required in each room using calibrated sound level meter. Measurements at 3 positions per room, A-weighted, with HVAC running at design airflow. Any room exceeding NC target by more than 2 dB requires remediation before acoustic treatment installation.