B3 YELLOW ZONE — HVAC EQUIPMENT MAP

TechTown Damascus | Basement 3, NW Corner (MediaVerse) | Scale 1:50 | 2026-03-04 v01
Layers shown: Zone boundary, Columns, HVAC indoor units, Air devices | All other layers OFF
0 1 2 3 4 5 6 7 1 2 3 4 meters CONCRETE (NW DIAGONAL) CONCRETE (NORTH) GYPSUM → SERVER RM B313 INTERIOR (DEMOLISH) 7.37 m (737 cm — South Wall) 4.31 m (431 cm — East Wall) ~6.15 m (614.8 cm — North Wall) 4.48 m (448 cm diagonal) 1.22 m (horiz. component) Column row (1.11m from S) COL-1 60 x 50 cm 3.34 m (334 cm) COL-2 ~55 x 50 cm ~2.57 m gap U380 DAIKIN VRF (Indoor Unit) U370/U371 ~2.7m east → DIFF 5 more diffusers 0.9-4.6m west → N S E W SCALE 1:50 0 1m 2m 3m YELLOW ZONE ~29.13 m2 LEGEND Zone boundary (concrete = solid, partition = dashed) Structural column Daikin VRF indoor unit (approximate position) Air device (diffuser/grille) SW (0, 0) SE (7.37, 0) NE (7.37, 4.31) NW (1.22, 4.31) SERVER ROOM B313 55-65 dB(A)
ZONE GEOMETRY (Trapezoid)
ParameterValue
ShapeRight Trapezoid
South wall (bottom, E-W)7.37 m (737 cm)
North wall (top, E-W)~6.15 m (614.8 cm)
East wall (right, N-S)4.31 m (431 cm)
NW diagonal wall4.48 m (448 cm)
Diagonal horizontal component1.22 m (122.2 cm)
Diagonal vertical component4.31 m (= east wall)
Diagonal angle from vertical~15.8 deg
Gross area29.13 m2
Ceiling to concrete slab3.50 m
Raw volume101.9 m3
Effective height (after float floor + acoustic ceiling)3.15 m
Effective volume~91.8 m3
VERTEX COORDINATES (origin at SW)
VertexX (m)Y (m)Description
SW0.000.00South wall, west end (diagonal base)
SE7.370.00South wall, east end
NE7.374.31North wall, east end
NW1.224.31North wall, west end (diagonal top)
WIDTH AT KEY LEVELS
LevelY from SouthWidth (E-W)
South wall0.00 m7.37 m
Column row1.11 m~7.06 m
Mid-height2.16 m~6.76 m
North wall4.31 m~6.15 m
COLUMN POSITIONS
ColumnSize (cm)X from SW (m)Y from South (m)Notes
COL-1 60 x 50 3.65 (west face)
4.25 (east face)
1.11 (south face)
1.61 (north face)
334 cm from diagonal wall at this height. Center at (3.95, 1.36)
COL-2 ~55 x 50 ~6.82 (west face)
~7.37 (east face)
1.11 (south face)
1.61 (north face)
Near/against east wall. Exact position TBD from DXF.
DAIKIN VRF INDOOR UNITS
UnitDXF BlockLocationStatus
U380 *U380 Inside zone, near SE corner
~6.88m E, ~0.50m N from SW
APPROXIMATE
U370 / U371 *U370 / *U371 ~2.7m EAST of zone (adjacent area) Outside zone
U328 *U328 ~10m+ east (different B3 area) Outside zone
Coordinate mapping is approximate. The furniture DXF (meters) and HVAC DXF (millimeters) use different origins. Positions derived from offset calculation: HVAC_X = Furniture_X x 1000 + 203,000. HVAC contractor must confirm exact unit positions on the updated floor plan.
AIR DEVICES (DIFFUSERS/GRILLES)
#DXF Coords (mm)Mapped PositionInside Zone?
1X: 252,428 | Y: 274,072~1.73m E, ~0.04m N from SWNear south wall
2X: 249,780 | Y: 274,421~0.9m west of zoneNo — outside
3X: 249,780 | Y: 273,376~0.9m west of zoneNo — outside
4X: 248,776 | Y: 274,421~1.9m west of zoneNo — outside
5X: 248,776 | Y: 273,376~1.9m west of zoneNo — outside
6X: 246,104 | Y: 274,073~4.6m west of zoneNo — outside
CRITICAL FINDING: Only 1 indoor unit (U380) and 1 diffuser appear to be inside/near the yellow zone. The remaining equipment (U370/U371 + 5 diffusers) serve adjacent areas WEST and EAST of the zone. This confirms the "last mile" approach — existing ductwork reaches the area but delivery points need to be redesigned for acoustic rooms.
ACOUSTIC HVAC STRATEGY
ActionDetail
Indoor unit (U380)Relocate to corridor/editing zone (non-critical area). Must NOT be in VO Live Room or Control Room.
Oversize final dropsIncrease duct diameter by 1-2 sizes to reduce velocity. Target: flow velocity < 3 m/s in duct.
Acoustic plenum boxesExpanded boxes with 50mm rockwool lining (60 kg/m3). Face area: 44x44 cm minimum for 600 CFM at 1.5 m/s.
Inline silencersRectangular baffle silencers. Max duct size 250mm to fit in 60cm ceiling space.
Flexible S-curveInside VO room: hard pipe transitions to flexible acoustic duct in S-curve. Breaks line-of-sight sound path.
Diffuser sizing~2.5x standard face area needed. Target: terminal velocity ≤ 1.5 m/s at diffuser face.
NC budgetHVAC alone must achieve NC-10 to NC-12 per duct run (margin for NC-15 total in VO room).
TechTown Acoustics 2.0 | MediaVerse B3 | Doc: HVAC/2026-03-04_v01_B3-Zone-Map-HVAC.html
Generated by Claude (Opus 4.6) | Coordinate mapping approximate — confirm with HVAC contractor overlay
Source DXFs: SD-HVAC-ALL-241225-V02 (HVAC) + B3 Final Furniture layout 03.03.2026 (Furniture)