HVAC Equipment Map — B3 Yellow Zone

Date: 2026-03-04 | Version: v01 ACTIVE | Author: Claude (Opus 4.6)


Source Files

FileLocationSizeLayers
HVAC DrawingSource/2026-03-04_v01_HVAC-All-Floors.dxf39 MB151 total, 33 HVAC-related
Furniture LayoutSource/2026-03-04_Furniture-Layout-Original-AutoCAD.dxf7.7 MB40 total, 0 HVAC
CRITICAL: The furniture layout DXF contains ZERO HVAC layers. All HVAC data is exclusively in the dedicated HVAC DXF.

Coordinate System Note

The two DXFs use different coordinate systems:

Cross-referencing relies on the B3 floor reference block FRU-B-3 at X: 263,875 | Y: 275,215 (HVAC DXF).


HVAC Layers Identified (33 layers)

Ductwork Layers

LayerDescription
MECH-Supply DuctMain supply air ductwork
MECH-RETURN DUCTMain return air ductwork
MECH-BRANCHBranch duct connections
MECH-EXHAUST DUCTExhaust air ducts
MECH-FRISH DUCTFresh air intake ducts
ME S.A DUCTSupply air duct (alternate naming)
ME R.A DuctReturn air duct (alternate naming)
Supply Air DuctSupply air duct (third naming variant)
Duct / Duct RGeneric duct layers
H-DUCTAdditional duct layer

Equipment Layers

LayerDescription
MECH-Indoor unitVRF indoor fan coil units (CRITICAL)
MECH-Indoor unit-ductConnection ducts to indoor units
MECH-Outdoor unitOutdoor condenser units
MECH-AHUAir Handling Units
MECH-FANFan components
MECH-VDVolume Dampers

Distribution Layers

LayerDescription
MECH-Blenum Box SupplyPlenum boxes (note: "Blenum" is DXF typo)
VI-AIR DEVICESDiffusers, grilles, air terminals
FLEXIBLE-DUCT / H-FLEXIBLEFlexible ductwork
MECH-Flex jointFlexible connections

Piping Layers

LayerDescription
MECH - Refrigerant PipesMain refrigerant piping
MECH-Refrigerant BranchesRefrigerant branch lines
MECH-PipGeneral piping

Annotation Layers

LayerDescription
MECH-TextHVAC text annotations
MECH-Space TagedMechanical space tags
MECH_ supply duct / MECH_flexVariant naming layers

Indoor Units Near B3 Yellow Zone

Reference: B3 floor marker at X: 263,875 | Y: 275,215

Primary Units (< 7,000 unit radius — likely serving B3 zone)

UnitBlockXYDist. from B3 RefNotes
1*U370260,783271,311~4,980Closest unit
2*U371260,783271,311~4,980Paired with U370 (same position)
3*U328268,410278,312~5,492NE quadrant
4*U380257,582273,611~6,494West side

Secondary Units (7,000–20,000 radius — adjacent zones or shared)

UnitBlockXYDist. from B3 Ref
5*U372253,795261,985~16,632
6*U377253,795261,985~16,632
7*U378253,795261,985~16,632
8*U379253,070262,078~17,010
9*U131280,734268,434~18,172
10*U104282,174269,793~19,085

Air Devices (Diffusers/Grilles) Near B3

VI-AIR DEVICES Layer — B3 Area

BlockXYDist. from B3 RefRotation
A$C2c00dd91252,428274,072~11,504
A$C2c00dd91249,780274,421~14,117270°
A$C2c00dd91249,780273,376~14,214270°
A$C2c00dd91248,776274,421~15,120270°
A$C2c00dd91248,776273,376~15,211270°
A$C2c00dd91246,104274,073~17,808

Scale factors: 25.05 (standard diffusers) and 37.58 (VCD devices)
Color: 10 (cyan)


Implications for Acoustic Design

1. "Work With What We Have" Strategy

Based on the DXF analysis, the existing HVAC installation includes:

2. Last-Mile Modification Plan (Confirmed Approach)

Per the HVAC coordination log, the agreed strategy is:

[KEEP AS-IS]                    [MODIFY - LAST MILE ONLY]

Main VRF piping ──────────┐
Main supply/return ducts ─┤
Branch ducts to zone ─────┤
                          │
Indoor unit position ─────┤     ← Move to corridor/editing (non-critical zone)
                          │
                          ├──── Oversize final drops (increase duct diameter)
                          ├──── Insert inline acoustic silencers (baffle boxes)
                          ├──── Transition: hard pipe → flexible acoustic duct
                          ├──── S-curve routing (break line-of-sight)
                          ├──── Expanded acoustic plenum boxes
                          └──── Oversized diffusers (target ≤ 1.5 m/s)

3. Plenum Box Sizing Requirements

Target: Terminal air velocity ≤ 1.5 m/s at diffuser face

Typical VRF indoor unit airflow: 400–800 CFM (190–380 L/s) per unit

Required Face AreaAt 1.5 m/sAt 2.0 m/s (relaxed)
400 CFM (190 L/s)0.127 m² (36×36 cm)0.095 m² (31×31 cm)
600 CFM (285 L/s)0.190 m² (44×44 cm)0.143 m² (38×38 cm)
800 CFM (380 L/s)0.253 m² (50×50 cm)0.190 m² (44×44 cm)

Standard commercial diffusers: Typically 2.5–4 m/s → we need ~2.5× the face area

4. Silencer Space Constraint

Available ceiling space: 60 cm (drop ceiling zone)

Typical rectangular silencers for VRF duct sizes:

Recommendation: Keep duct sizes ≤ 250 mm in the ceiling zone, or use horizontal-run silencers that fit within 60 cm height.

5. NC Budget Per Duct Run

For NC-15 total in VO room, HVAC contribution must be NC-10 to NC-12:

ComponentTarget NCAchieved By
Supply duct to VO roomNC-102× inline silencers + plenum box
Return duct from VO roomNC-101× inline silencer + plenum box
Supply duct to Control roomNC-201× inline silencer
Indoor unit radiated noiseNC-10Unit located outside critical rooms
Diffuser self-noiseNC-10Oversized face area (≤ 1.5 m/s)
Duct breakout noiseNC-15Lined ductwork (25 mm acoustic lining)

Outstanding Actions (From HVAC Coordination Log)


This document should be updated when HVAC team provides floor plan review and airflow data.