B3 YELLOW ZONE — HVAC EQUIPMENT MAP

TechTown Damascus | Basement 3, NW Corner (MediaVerse) | Scale 1:50 | 2026-03-04 v02 CORRECTED
Layers shown: Zone boundary, Columns, HVAC indoor units, Air devices | All other layers OFF
v02 CORRECTION (from v01): North wall is 860 cm (8.60 m), not 614.8 cm. Room WIDENS going north — the NW diagonal extends OUTWARD (west).
-1 0 1 2 3 4 5 6 7 1 2 3 4 meters (from SW origin) CONCRETE (NW DIAGONAL) CONCRETE (NORTH) — 8.60 m GYPSUM → SERVER RM B313 INTERIOR (DEMOLISH) ROOM WIDENS ← N 7.37 m (737 cm — South Wall) 4.31 m (431 cm — East Wall) 8.60 m (860 cm — North Wall) ← CORRECTED 4.48 m (448 cm diagonal) 1.23 m (horiz. component — extends WEST) Column row (1.11m from S) COL-1 60 x 50 cm COL-2 ~55 x 50 cm COL gap ~2.57 m | Row span: 334+60+333 = 727 cm U380 DAIKIN VRF (Indoor Unit) U370/U371 ~2.7m east → DIFF 5 more diffusers 0.9-4.6m west → N S E W SCALE 1:50 0 1m 2m 3m YELLOW ZONE 34.42 m² LEGEND Zone boundary (concrete = solid, partition = dashed) Structural column Daikin VRF indoor unit (approximate position) Air device (diffuser/grille) SW (0, 0) SE (7.37, 0) NE (7.37, 4.31) NW (-1.23, 4.31) SERVER ROOM B313 55-65 dB(A)
ZONE GEOMETRY (Trapezoid) — CORRECTED v02
ParameterValue
ShapeRight Trapezoid
South wall (bottom, E-W)7.37 m (737 cm)
North wall (top, E-W)8.60 m (860 cm) ← CORRECTED
East wall (right, N-S)4.31 m (431 cm)
NW diagonal wall4.48 m (448 cm)
Diagonal horizontal component1.23 m (123 cm) — extends WEST
Diagonal vertical component4.31 m (= east wall)
Diagonal angle from vertical~15.9°
Gross area34.42 m² ← CORRECTED
Ceiling to concrete slab3.50 m
Raw volume120.5 m³ ← CORRECTED
Effective height (after float floor + acoustic ceiling)3.15 m
Effective volume108.4 m³ ← CORRECTED
VERTEX COORDINATES (origin at SW) — CORRECTED v02
VertexX (m)Y (m)Description
SW0.000.00South wall, west end (diagonal base)
SE7.370.00South wall, east end
NE7.374.31North wall, east end
NW-1.234.31North wall, west end (1.23m WEST of SW)
WIDTH AT KEY LEVELS (Room WIDENS northward)
LevelY from SouthWidth (E-W)
South wall0.00 m7.37 m (narrowest)
Column row1.11 m7.69 m
Mid-height2.16 m7.99 m
North wall4.31 m8.60 m (widest)
Width formula (CORRECTED): W(Y) = 7.37 + (Y / 4.31) × 1.23 meters
Room WIDENS going north. Previous v01 had the sign wrong (minus instead of plus).
COLUMN POSITIONS
ColumnSize (cm)X from SW (m)Y from South (m)Notes
COL-1 60 x 50 3.65 (west face)
4.25 (east face)
1.11 (south face)
1.61 (north face)
Center at (3.95, 1.36)
COL-2 ~55 x 50 ~6.82 (west face)
~7.37 (east face)
1.11 (south face)
1.61 (north face)
Near/against east wall. Exact position TBD from DXF.
DAIKIN VRF INDOOR UNITS
UnitDXF BlockLocationStatus
U380 *U380 Inside zone, near SE corner
~6.88m E, ~0.50m N from SW
APPROXIMATE
U370 / U371 *U370 / *U371 ~2.7m EAST of zone (adjacent area) Outside zone
U328 *U328 ~10m+ east (different B3 area) Outside zone
Coordinate mapping is approximate. The furniture DXF (meters) and HVAC DXF (millimeters) use different origins. Positions derived from offset calculation: HVAC_X = Furniture_X x 1000 + 203,000. HVAC contractor must confirm exact unit positions on the updated floor plan.
AIR DEVICES (DIFFUSERS/GRILLES)
#DXF Coords (mm)Mapped PositionInside Zone?
1X: 252,428 | Y: 274,072~1.73m E, ~0.04m N from SWNear south wall
2X: 249,780 | Y: 274,421~0.9m west of zoneNo — outside
3X: 249,780 | Y: 273,376~0.9m west of zoneNo — outside
4X: 248,776 | Y: 274,421~1.9m west of zoneNo — outside
5X: 248,776 | Y: 273,376~1.9m west of zoneNo — outside
6X: 246,104 | Y: 274,073~4.6m west of zoneNo — outside
CRITICAL FINDING: Only 1 indoor unit (U380) and 1 diffuser appear to be inside/near the yellow zone. The remaining equipment (U370/U371 + 5 diffusers) serve adjacent areas WEST and EAST of the zone. This confirms the "last mile" approach — existing ductwork reaches the area but delivery points need to be redesigned for acoustic rooms.
ACOUSTIC HVAC STRATEGY
ActionDetail
Indoor unit (U380)Relocate to corridor/editing zone (non-critical area). Must NOT be in VO Live Room or Control Room.
Oversize final dropsIncrease duct diameter by 1-2 sizes to reduce velocity. Target: flow velocity < 3 m/s in duct.
Acoustic plenum boxesExpanded boxes with 50mm rockwool lining (60 kg/m³). Face area: 44x44 cm minimum for 600 CFM at 1.5 m/s.
Inline silencersRectangular baffle silencers. Max duct size 250mm to fit in 60cm ceiling space.
Flexible S-curveInside VO room: hard pipe transitions to flexible acoustic duct in S-curve. Breaks line-of-sight sound path.
Diffuser sizing~2.5x standard face area needed. Target: terminal velocity ≤ 1.5 m/s at diffuser face.
NC budgetHVAC alone must achieve NC-10 to NC-12 per duct run (margin for NC-15 total in VO room).
TechTown Acoustics 2.0 | MediaVerse B3 | Doc: HVAC/2026-03-04_v02_B3-Zone-Map-HVAC.html
Generated by Claude (Opus 4.6) | v02 CORRECTED: North wall 860 cm, area 34.42 m²
Coordinate mapping approximate — confirm with HVAC contractor overlay
Source DXFs: SD-HVAC-ALL-241225-V02 (HVAC) + B3 Final Furniture layout 03.03.2026 (Furniture)
Authoritative dimensions: Source/2026-03-04_MediaVerse-Dimensions-Corrected.pdf