THIS FILE IS THE SINGLE SOURCE OF TRUTH (SSOT) FOR ALL HVAC DATA.
All layout designs MUST respect these values. Indoor unit positions, ductwork, and refrigerant routing are EXISTING INFRASTRUCTURE that can only be modified through the agreed "last-mile" approach with the HVAC contractor.
SUPERSEDES: U380 position from DXF extraction (was approximate, now corrected by contractor drawing).
B3 Yellow Zone + adjacent areas (server room, corridors)
Date Received
2026-03-05
POSITION CONFIDENCE: Equipment specifications (TR, CFM, m³/h) are EXACT — read directly from drawing labels. Physical positions within the zone are APPROXIMATE — estimated from PDF visual analysis. For final construction, request exact coordinates from HVAC contractor's AutoCAD source file.
2. Indoor Units Inside Zone
Unit
Capacity
Airflow
Fresh Air
Return Air
Position (zone cm)
Confidence
B3-VRF-IDU-03
1.0 TR (3.52 kW)
318 CFM (150 L/s)
FA-10
RA-200
~(310, 225)
APPROX
B3-VRF-IDU-04
1.0 TR (3.52 kW)
318 CFM (150 L/s)
FA-58
RA-260
~(250, 75)
APPROX
Capacity Summary
Parameter
Value
Total cooling capacity
2.0 TR (7.04 kW) EXACT
Total airflow
636 CFM (300 L/s) EXACT
Units
2 × ceiling-mounted VRF cassettes
Cooling per m²
7,040 / 34.42 = 205 W/m²
CAPACITY CHECK: 205 W/m² provides adequate headroom for studio use with:
Video lighting rigs (~500-2000W)
Multiple computers + monitors (~300-600W)
Body heat from talent + crew (75W × 4 people = 300W)
Estimated studio heat load: ~200-250 W/m². Upgraded 2.0 TR system provides cooling capacity of 205 W/m² (7,040 W / 34.42 m²). IDU upgrade from 0.75 TR to 1.0 TR per unit — same fan speed (318 CFM), same ductwork, extra cooling via higher refrigerant flow.
Previous DXF Data — SUPERSEDED
The DXF extraction report identified U380 at zone position (688, 50) — near the SE corner. The B3-Existing PDF shows IDU-03 and IDU-04 in the CENTER-WEST area. The PDF is the HVAC contractor's design drawing and SUPERSEDES the DXF extraction for unit positions.
U380 mapping: U380 likely corresponds to one of IDU-03/IDU-04 (different naming conventions between architect DXF and HVAC contractor drawing). The DXF block position was either a placeholder or referenced a different revision.
3. Air Devices (Diffusers)
Type
Rating
Qty Inside Zone
Approx Positions
Confidence
AVD-09
540 m³/h each
3
Spread along E-W duct run, center area: ~(330, 190), ~(390, 160), ~(450, 130)
APPROX
Total diffuser capacity: 3 × 540 = 1,620 m³/hEXACT
4. Ductwork
Main Duct Runs
Duct
Size (mm)
Routing
Approx Y Position
Confidence
Main supply duct
300 × 200
E-W through center of zone, along column line
Y ≈ 140-200 cm from south
APPROX
Branch ducts
Smaller (est. 200 × 150)
From main duct to AVD-09 diffusers
Various
APPROX
DUCT BAND RULE: The main ductwork occupies a horizontal band from Y≈110 to Y≈230 (roughly aligned with the structural column line at Y=111-161). Any partition wall running N-S through this band will CROSS the ductwork and require acoustic penetration treatment.
Supply/Return Flow Bars (North Wall)
Type
Spec
Position
Approx X Range (zone cm)
S.FLOW BAR (Supply)
2 slots, 50mm wide, L=1.5m, 2 FLEXIBLE 150mm+VD
North wall, NW portion
X ≈ -80 → 70 (diagonal area)
S.FLOW BAR (Supply)
2 slots, 50mm wide, L=1.0m
North wall, left of center
X ≈ 70 → 170
R.FLOW BAR (Return)
2 slots, 50mm wide, L=1.5m
North wall, center-east portion
X ≈ 400 → 550
R.FLOW BAR (Return)
2 slots, 50mm wide, L=1.0m
West/diagonal wall area
Y ≈ 250-350 (on diagonal)
NORTH WALL SPLIT RULE: The north wall HVAC distribution splits at approximately X ≈ 396 cm (verified: 5191mm from NW corner = X = -123 + 519.1 = 396.1 cm). West of X≈396: Supply bars (feed air INTO zone) — serves the NW area East of X≈396: Return bars (extract air FROM zone) — serves the NE area
Dimension verification: 5191 + 3410 = 8601 = 8600mm (north wall) -- OK
5. Refrigerant Piping
Line
Size
Routing
Confidence
Liquid line
1/2" (12.7mm)
Along south wall, E-W
EXACT (from label)
Gas line
5/8" (15.9mm)
Along south wall, E-W
EXACT (from label)
Branch liquid
1/4" (6.35mm)
From south wall up to indoor units
EXACT (from label)
Branch gas
3/8" (9.53mm)
From south wall up to indoor units
EXACT (from label)
Identification: Lines marked "102F" in drawing
REFRIGERANT ROUTING RULE: Main refrigerant lines run along the SOUTH WALL at floor/ceiling level. Branch lines rise from the south wall to reach the indoor units. Any partition wall crossing the south wall area must provide rubber-grommeted penetrations for refrigerant lines, with vibration isolation clips every 60cm.
6. Adjacent HVAC (Outside Zone — Context Only)
Unit/Device
Spec
Location
Relevance to Zone
B3-Split-IDU-16
2.0 TR, 647 CFM
NE of zone — ROOM-SERVER
NOISE SOURCE: Server room HVAC generates noise that transmits through east wall
AUD-24
1,000 m³/h
NE of zone
Air noise through east wall
AUD-36
2,100 m³/h
East of zone — ROOM-SERVER
High-volume air movement = noise source
AVD-24
840 m³/h
SE of zone
Possible flanking through south/east corner
SERVER ROOM HVAC NOISE: B313 has 2.0 TR split unit + 2,100 m³/h air device + 1,000 m³/h air device. This is a significant noise source (estimated 55-65 dB(A)) adjacent to our east wall. The east wall STC rating must account for this combined HVAC + server equipment noise.
7. HVAC-to-Zone Position Map
8. Locked Rules for Layout Design
RULE 1 — UNIT CONSERVATION
The zone has exactly 2 indoor units (IDU-03, IDU-04) totaling 2.0 TR / 636 CFM. IDUs upgraded from 0.75 to 1.0 TR each (same fan speed, same ductwork). Layouts must distribute this capacity across all rooms.
RULE 2 — DUCT BAND CONSTRAINT
Main ductwork runs E-W through the zone at Y ≈ 110-230 cm (column line band). Any N-S partition wall crossing this band requires:
Acoustic duct boot at each penetration
Flex connection (min 30cm) on both sides of wall
Inline silencer (min 600mm long) on the quiet-room side
Fire damper per code
Each penetration degrades wall STC by 2-5 points unless properly treated
RULE 3 — NORTH WALL DISTRIBUTION SPLIT
The north wall HVAC splits at X ≈ 396 cm:
West of X=396: Supply flow bars (2.5m total length)
East of X=396: Return flow bars (1.5m total length)
Any room in the NW area can leverage existing supply bars for supplemental air supply. Rooms in the NE area can use existing return bars.
RULE 4 — REFRIGERANT ROUTING
Main refrigerant lines run along the south wall. Branch lines rise vertically to indoor units. Relocating an indoor unit:
300×300mm duct → 400×400×1200mm silencer — DOES NOT FIT vertically
Keep duct sizes ≤ 250mm in the ceiling zone, or use horizontal-run silencers.
9. Quick Reference Block
═══════════════════════════════════════════════════════
SSOT-HVAC — LOCKED VALUES (2026-03-05)
═══════════════════════════════════════════════════════
INDOOR UNITS:
IDU-03: 1.0 TR, 318 CFM, FA-10, RA-200 ~(310, 225)
IDU-04: 1.0 TR, 318 CFM, FA-58, RA-260 ~(250, 75)
Total: 2.0 TR (7.04 kW), 636 CFM
DIFFUSERS:
3× AVD-09 @ 540 m³/h = 1,620 m³/h total
DUCTWORK:
Main: 300×200mm, E-W run at Y≈140-200
Duct band: Y ≈ 110–230 (column line zone)
NORTH WALL DISTRIBUTION:
Supply zone: NW to X≈396 (bars total 2.5m)
Return zone: X≈396 to NE (bar 1.5m)
REFRIGERANT:
Main: ½" liquid + ⅝" gas along SOUTH WALL
Branch: ¼" liquid + ⅜" gas rising to units
ID: "102F"
ADJACENT NOISE (B313 Server Room):
IDU-16: 2.0 TR + AUD-36: 2,100 m³/h
Combined: 55–65 dB(A) through east wall
CEILING PLENUM: 60 cm (silencer max: 250mm duct)
COOLING DENSITY: 205 W/m² (7,040 W / 34.42 m²)
UNIT SPATIAL BIAS: WEST-CENTER (X≈250-310)
Optimal partition: X ≈ 250–300 (splits units)
Worst partition: X < 220 (all HVAC on east side)
═══════════════════════════════════════════════════════
Source: B3-Existing.pdf | Supersedes: DXF U380 data
═══════════════════════════════════════════════════════
10. Reconciliation with SSOT-GEOMETRY
Parameter
SSOT-GEOMETRY
SSOT-HVAC
Status
Zone area
34.42 m²
(uses same)
CONSISTENT
Column positions
COL-W (364,136), COL-E (757,133)
Duct band aligns with column line
CONSISTENT
East wall
X=737, 10cm gypsum to B313
B313 has 2.0 TR unit = noise source
CONSISTENT
VRF unit position
"U380 near SE corner"
IDU-03 ~(310,225), IDU-04 ~(250,75)
SUPERSEDED -- PDF is authoritative
Ceiling space
Slab 350cm, effective 275cm
60cm plenum for silencers
CONSISTENT (350-15-60=275)
HVAC system
Daikin VRF
Daikin VRF confirmed (IDU-03, IDU-04)
CONSISTENT
ACTION REQUIRED: Update SSOT-GEOMETRY.md Section "Key Project Parameters" to reference IDU-03 and IDU-04 instead of "U380 near SE corner." The geometry values remain unchanged — only the HVAC unit reference needs updating to match this SSOT.
11. Authoritative Files
This file: SSOT-HVAC.html — Single Source of Truth for HVAC