SSOT — HVAC (B3 Yellow Zone)

Status: LOCKED 2026-03-05 | Source: B3-Existing.pdf (HVAC Contractor Drawing) | Cross-ref: SSOT-GEOMETRY.md (Zone Geometry)

THIS FILE IS THE SINGLE SOURCE OF TRUTH (SSOT) FOR ALL HVAC DATA.
All layout designs MUST respect these values. Indoor unit positions, ductwork, and refrigerant routing are EXISTING INFRASTRUCTURE that can only be modified through the agreed "last-mile" approach with the HVAC contractor.

SUPERSEDES: U380 position from DXF extraction (was approximate, now corrected by contractor drawing).

1. Source Document

PropertyValue
FileB3-Existing.pdf
TypeHVAC Contractor Installation Drawing — As-Designed
SystemDaikin VRF (Variable Refrigerant Flow)
CoverageB3 Yellow Zone + adjacent areas (server room, corridors)
Date Received2026-03-05
POSITION CONFIDENCE: Equipment specifications (TR, CFM, m³/h) are EXACT — read directly from drawing labels. Physical positions within the zone are APPROXIMATE — estimated from PDF visual analysis. For final construction, request exact coordinates from HVAC contractor's AutoCAD source file.

2. Indoor Units Inside Zone

UnitCapacityAirflowFresh AirReturn AirPosition (zone cm)Confidence
B3-VRF-IDU-03 1.0 TR (3.52 kW) 318 CFM (150 L/s) FA-10 RA-200 ~(310, 225) APPROX
B3-VRF-IDU-04 1.0 TR (3.52 kW) 318 CFM (150 L/s) FA-58 RA-260 ~(250, 75) APPROX

Capacity Summary

ParameterValue
Total cooling capacity2.0 TR (7.04 kW) EXACT
Total airflow636 CFM (300 L/s) EXACT
Units2 × ceiling-mounted VRF cassettes
Cooling per m²7,040 / 34.42 = 205 W/m²
CAPACITY CHECK: 205 W/m² provides adequate headroom for studio use with: Estimated studio heat load: ~200-250 W/m². Upgraded 2.0 TR system provides cooling capacity of 205 W/m² (7,040 W / 34.42 m²). IDU upgrade from 0.75 TR to 1.0 TR per unit — same fan speed (318 CFM), same ductwork, extra cooling via higher refrigerant flow.

Previous DXF Data — SUPERSEDED

The DXF extraction report identified U380 at zone position (688, 50) — near the SE corner. The B3-Existing PDF shows IDU-03 and IDU-04 in the CENTER-WEST area. The PDF is the HVAC contractor's design drawing and SUPERSEDES the DXF extraction for unit positions.

U380 mapping: U380 likely corresponds to one of IDU-03/IDU-04 (different naming conventions between architect DXF and HVAC contractor drawing). The DXF block position was either a placeholder or referenced a different revision.

3. Air Devices (Diffusers)

TypeRatingQty Inside ZoneApprox PositionsConfidence
AVD-09 540 m³/h each 3 Spread along E-W duct run, center area: ~(330, 190), ~(390, 160), ~(450, 130) APPROX

Total diffuser capacity: 3 × 540 = 1,620 m³/h EXACT


4. Ductwork

Main Duct Runs

DuctSize (mm)RoutingApprox Y PositionConfidence
Main supply duct 300 × 200 E-W through center of zone, along column line Y ≈ 140-200 cm from south APPROX
Branch ducts Smaller (est. 200 × 150) From main duct to AVD-09 diffusers Various APPROX
DUCT BAND RULE: The main ductwork occupies a horizontal band from Y≈110 to Y≈230 (roughly aligned with the structural column line at Y=111-161). Any partition wall running N-S through this band will CROSS the ductwork and require acoustic penetration treatment.

Supply/Return Flow Bars (North Wall)

TypeSpecPositionApprox X Range (zone cm)
S.FLOW BAR (Supply) 2 slots, 50mm wide, L=1.5m, 2 FLEXIBLE 150mm+VD North wall, NW portion X ≈ -80 → 70 (diagonal area)
S.FLOW BAR (Supply) 2 slots, 50mm wide, L=1.0m North wall, left of center X ≈ 70 → 170
R.FLOW BAR (Return) 2 slots, 50mm wide, L=1.5m North wall, center-east portion X ≈ 400 → 550
R.FLOW BAR (Return) 2 slots, 50mm wide, L=1.0m West/diagonal wall area Y ≈ 250-350 (on diagonal)
NORTH WALL SPLIT RULE: The north wall HVAC distribution splits at approximately X ≈ 396 cm (verified: 5191mm from NW corner = X = -123 + 519.1 = 396.1 cm).
West of X≈396: Supply bars (feed air INTO zone) — serves the NW area
East of X≈396: Return bars (extract air FROM zone) — serves the NE area
Dimension verification: 5191 + 3410 = 8601 = 8600mm (north wall) -- OK

5. Refrigerant Piping

LineSizeRoutingConfidence
Liquid line 1/2" (12.7mm) Along south wall, E-W EXACT (from label)
Gas line 5/8" (15.9mm) Along south wall, E-W EXACT (from label)
Branch liquid 1/4" (6.35mm) From south wall up to indoor units EXACT (from label)
Branch gas 3/8" (9.53mm) From south wall up to indoor units EXACT (from label)

Identification: Lines marked "102F" in drawing

REFRIGERANT ROUTING RULE: Main refrigerant lines run along the SOUTH WALL at floor/ceiling level. Branch lines rise from the south wall to reach the indoor units. Any partition wall crossing the south wall area must provide rubber-grommeted penetrations for refrigerant lines, with vibration isolation clips every 60cm.

6. Adjacent HVAC (Outside Zone — Context Only)

Unit/DeviceSpecLocationRelevance to Zone
B3-Split-IDU-16 2.0 TR, 647 CFM NE of zone — ROOM-SERVER NOISE SOURCE: Server room HVAC generates noise that transmits through east wall
AUD-24 1,000 m³/h NE of zone Air noise through east wall
AUD-36 2,100 m³/h East of zone — ROOM-SERVER High-volume air movement = noise source
AVD-24 840 m³/h SE of zone Possible flanking through south/east corner
SERVER ROOM HVAC NOISE: B313 has 2.0 TR split unit + 2,100 m³/h air device + 1,000 m³/h air device. This is a significant noise source (estimated 55-65 dB(A)) adjacent to our east wall. The east wall STC rating must account for this combined HVAC + server equipment noise.

7. HVAC-to-Zone Position Map

SSOT-HVAC — Equipment Overlay on Zone Geometry North ↑ — Matching reference orientation — svg_y = 431 - zone_y COL-W COL-E X=396 DUCT BAND Y≈110-230 300×200 DUCT RUN (E-W) IDU 03 1.0 TR ~(310,225) IDU 04 1.0 TR ~(250,75) AVD AVD AVD 540 m³/h ea S.FLOW L=1.5m S.FLOW L=1.0m R.FLOW L=1.5m R.FLOW L=1.0m REFRIGERANT 102F (½" + ⅝" liquid/gas) ¼"+⅜" branch W W NORTH WALL 860 cm SOUTH WALL 737 cm EAST 431 cm DIAGONAL 448 5191mm (supply zone) 3410mm (return zone) Indoor Unit (VRF) Diffuser (AVD-09) Supply Bar Return Bar Refrigerant Line Duct Run B313 SERVER ROOM (55-65 dBA)

8. Locked Rules for Layout Design

RULE 1 — UNIT CONSERVATION
The zone has exactly 2 indoor units (IDU-03, IDU-04) totaling 2.0 TR / 636 CFM. IDUs upgraded from 0.75 to 1.0 TR each (same fan speed, same ductwork). Layouts must distribute this capacity across all rooms.
RULE 2 — DUCT BAND CONSTRAINT
Main ductwork runs E-W through the zone at Y ≈ 110-230 cm (column line band). Any N-S partition wall crossing this band requires:
RULE 3 — NORTH WALL DISTRIBUTION SPLIT
The north wall HVAC splits at X ≈ 396 cm: Any room in the NW area can leverage existing supply bars for supplemental air supply. Rooms in the NE area can use existing return bars.
RULE 4 — REFRIGERANT ROUTING
Main refrigerant lines run along the south wall. Branch lines rise vertically to indoor units. Relocating an indoor unit:
RULE 5 — NC COMPLIANCE PATH
Indoor units generate 25-40 dB(A) at 1m (depending on fan speed). For NC compliance:
Room NC TargetUnit Placement RequirementDuct Treatment
NC-20 (VO)Unit MUST be OUTSIDE the room2× silencers + plenum + flex S-curve + oversized diffuser (≤1.5 m/s)
NC-25 (Control)Unit MUST be OUTSIDE the room1× silencer + plenum + flex
NC-30 (Studio)Unit in adjacent space (editing/corridor)1× silencer + lined duct
NC-35 (Editing)Unit can be above (in ceiling plenum)Basic silencer + flex connection
RULE 6 — UNIT SPATIAL BIAS
Both indoor units are in the WEST-CENTER of the zone (X ≈ 250-310). This creates a spatial bias:
RULE 7 — SILENCER SPACE CONSTRAINT
Available ceiling plenum: 60 cm (slab at 350cm, acoustic ceiling at 275cm above float floor). Silencer sizing: Keep duct sizes ≤ 250mm in the ceiling zone, or use horizontal-run silencers.

9. Quick Reference Block

═══════════════════════════════════════════════════════
  SSOT-HVAC — LOCKED VALUES (2026-03-05)
═══════════════════════════════════════════════════════

INDOOR UNITS:
  IDU-03: 1.0 TR, 318 CFM, FA-10, RA-200  ~(310, 225)
  IDU-04: 1.0 TR, 318 CFM, FA-58, RA-260  ~(250, 75)
  Total:  2.0 TR (7.04 kW), 636 CFM

DIFFUSERS:
  3× AVD-09 @ 540 m³/h = 1,620 m³/h total

DUCTWORK:
  Main: 300×200mm, E-W run at Y≈140-200
  Duct band: Y ≈ 110–230 (column line zone)

NORTH WALL DISTRIBUTION:
  Supply zone: NW to X≈396 (bars total 2.5m)
  Return zone: X≈396 to NE (bar 1.5m)

REFRIGERANT:
  Main: ½" liquid + ⅝" gas along SOUTH WALL
  Branch: ¼" liquid + ⅜" gas rising to units
  ID: "102F"

ADJACENT NOISE (B313 Server Room):
  IDU-16: 2.0 TR + AUD-36: 2,100 m³/h
  Combined: 55–65 dB(A) through east wall

CEILING PLENUM: 60 cm (silencer max: 250mm duct)
COOLING DENSITY: 205 W/m² (7,040 W / 34.42 m²)

UNIT SPATIAL BIAS: WEST-CENTER (X≈250-310)
  Optimal partition: X ≈ 250–300 (splits units)
  Worst partition:   X < 220 (all HVAC on east side)

═══════════════════════════════════════════════════════
  Source: B3-Existing.pdf | Supersedes: DXF U380 data
═══════════════════════════════════════════════════════

10. Reconciliation with SSOT-GEOMETRY

ParameterSSOT-GEOMETRYSSOT-HVACStatus
Zone area34.42 m²(uses same)CONSISTENT
Column positionsCOL-W (364,136), COL-E (757,133)Duct band aligns with column lineCONSISTENT
East wallX=737, 10cm gypsum to B313B313 has 2.0 TR unit = noise sourceCONSISTENT
VRF unit position"U380 near SE corner"IDU-03 ~(310,225), IDU-04 ~(250,75)SUPERSEDED -- PDF is authoritative
Ceiling spaceSlab 350cm, effective 275cm60cm plenum for silencersCONSISTENT (350-15-60=275)
HVAC systemDaikin VRFDaikin VRF confirmed (IDU-03, IDU-04)CONSISTENT
ACTION REQUIRED: Update SSOT-GEOMETRY.md Section "Key Project Parameters" to reference IDU-03 and IDU-04 instead of "U380 near SE corner." The geometry values remain unchanged — only the HVAC unit reference needs updating to match this SSOT.